Residential Conduit Fill Calculator

Calculate conduit fill for residential electrical projects with our free, NEC-compliant calculator. This tool is specifically designed for common home wiring scenarios including 15A and 20A branch circuits, appliance circuits, and general residential installations.

Whether you're running circuits for lighting, receptacles, kitchen appliances, or air conditioning units, our calculator ensures your residential conduit installations meet all National Electrical Code requirements for safe and compliant home wiring.

Input Parameters

Conductors

Results

Enter conduit and wire information to see results

NEC Fill Requirements

According to NEC Chapter 9, Table 1: 1 conductor = 53% max, 2 conductors = 31% max, 3+ conductors = 40% max, Nipples = 60% max

Common Residential Circuit Examples

15A & 20A Branch Circuits:

  • General Lighting (15A)
    14 AWG THHN, 1/2" or 3/4" EMT
  • Receptacle Circuits (20A)
    12 AWG THHN, 1/2" or 3/4" EMT
  • Bathroom Circuits (20A)
    12 AWG THHN, 1/2" EMT

Appliance Circuits:

  • Kitchen Small Appliances (20A)
    12 AWG THHN, 1/2" or 3/4" EMT
  • Dishwasher/Disposal (20A)
    12 AWG THHN, 1/2" EMT
  • AC/Heat Pump (30-50A)
    10-6 AWG THHN, 3/4" to 1" EMT