How Many 1 AWG Wires Fit in RMC Conduit?
Complete NEC-compliant fill chart for 1 AWG THHN wires in Rigid Metal Conduit (RMC) conduit. Maximum wire counts for all standard conduit sizes.
Quick Answer
For 1 AWG THHN wires in RMC conduit at 40% fill (3+ wires):
- • 3/4" RMC: 1 wires
- • 1" RMC: 2 wires
- • 1-1/4" RMC: 3 wires
1 AWG in RMC Conduit Fill Chart
Conduit Size | Max Wires (40% Fill) | Fill % | Max Wires (Nipple 60%) | Fill % |
---|---|---|---|---|
3/4" | 1 | 28% | 2 | 57% |
1" | 2 | 35% | 3 | 53% |
1-1/4" | 3 | 31% | 5 | 51% |
1-1/2" | 5 | 38% | 7 | 53% |
2" | 8 | 37% | 13 | 60% |
2-1/2" | 15 | 39% | 23 | 60% |
3" | 22 | 39% | 34 | 60% |
3-1/2" | 29 | 39% | 44 | 59% |
4" | 38 | 40% | 57 | 60% |
Understanding the Fill Chart
According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:
- 1 conductor: 53% fill maximum
- 2 conductors: 31% fill maximum
- 3 or more conductors: 40% fill maximum
- Nipples (24" or less): 60% fill maximum
This chart shows the maximum number of 1 AWG THHN conductors that can fit in each RMC conduit size while maintaining NEC compliance.
Calculation Example
Question: How many 1 AWG THHN wires can fit in 1" RMC conduit?
Wire area: 0.1562 sq in per conductor
Conduit internal area: 0.887 sq in
Allowable fill (40%): 0.3548 sq in
Maximum wires: 0.3548 ÷ 0.1562 = 2 wires
Answer: You can fit up to 2 wires of 1 AWG THHN in 1" RMC conduit.