How Many 8 AWG Wires Fit in FMC Conduit?

Complete NEC-compliant fill chart for 8 AWG THHN wires in Flexible Metal Conduit (FMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 8 AWG THHN wires in FMC conduit at 40% fill (3+ wires):

  • • 1/2" FMC: 3 wires
  • • 3/4" FMC: 5 wires
  • • 1" FMC: 8 wires

8 AWG in FMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 3 36% 4 49%
3/4" 5 36% 8 58%
1" 8 36% 13 58%
1-1/4" 14 38% 22 59%
1-1/2" 20 39% 31 60%
2" 34 40% 51 60%
2-1/2" 57 40% 86 60%
3" 88 40% 132 60%
3-1/2" 115 40% 173 60%
4" 146 40% 220 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 8 AWG THHN conductors that can fit in each FMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 8 AWG THHN wires can fit in 3/4" FMC conduit?

Wire area: 0.0366 sq in per conductor

Conduit internal area: 0.508 sq in

Allowable fill (40%): 0.2032 sq in

Maximum wires: 0.2032 ÷ 0.0366 = 5 wires

Answer: You can fit up to 5 wires of 8 AWG THHN in 3/4" FMC conduit.