How Many 8 AWG Wires Fit in FMC Conduit?
Complete NEC-compliant fill chart for 8 AWG THHN wires in Flexible Metal Conduit (FMC) conduit. Maximum wire counts for all standard conduit sizes.
Quick Answer
For 8 AWG THHN wires in FMC conduit at 40% fill (3+ wires):
- • 1/2" FMC: 3 wires
- • 3/4" FMC: 5 wires
- • 1" FMC: 8 wires
8 AWG in FMC Conduit Fill Chart
Conduit Size | Max Wires (40% Fill) | Fill % | Max Wires (Nipple 60%) | Fill % |
---|---|---|---|---|
1/2" | 3 | 36% | 4 | 49% |
3/4" | 5 | 36% | 8 | 58% |
1" | 8 | 36% | 13 | 58% |
1-1/4" | 14 | 38% | 22 | 59% |
1-1/2" | 20 | 39% | 31 | 60% |
2" | 34 | 40% | 51 | 60% |
2-1/2" | 57 | 40% | 86 | 60% |
3" | 88 | 40% | 132 | 60% |
3-1/2" | 115 | 40% | 173 | 60% |
4" | 146 | 40% | 220 | 60% |
Understanding the Fill Chart
According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:
- 1 conductor: 53% fill maximum
- 2 conductors: 31% fill maximum
- 3 or more conductors: 40% fill maximum
- Nipples (24" or less): 60% fill maximum
This chart shows the maximum number of 8 AWG THHN conductors that can fit in each FMC conduit size while maintaining NEC compliance.
Calculation Example
Question: How many 8 AWG THHN wires can fit in 3/4" FMC conduit?
Wire area: 0.0366 sq in per conductor
Conduit internal area: 0.508 sq in
Allowable fill (40%): 0.2032 sq in
Maximum wires: 0.2032 ÷ 0.0366 = 5 wires
Answer: You can fit up to 5 wires of 8 AWG THHN in 3/4" FMC conduit.