How Many 4/0 AWG Wires Fit in IMC Conduit?

Complete NEC-compliant fill chart for 4/0 AWG THHN wires in Intermediate Metal Conduit (IMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 4/0 AWG THHN wires in IMC conduit at 40% fill (3+ wires):

  • • 1" IMC: 1 wires
  • • 1-1/4" IMC: 1 wires
  • • 1-1/2" IMC: 2 wires

4/0 AWG in IMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1" 1 39% 1 39%
1-1/4" 1 22% 2 45%
1-1/2" 2 33% 3 50%
2" 3 30% 5 50%
2-1/2" 6 35% 10 58%
3" 10 38% 15 57%
3-1/2" 13 38% 20 59%
4" 17 40% 25 58%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 4/0 AWG THHN conductors that can fit in each IMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 4/0 AWG THHN wires can fit in 1-1/4" IMC conduit?

Wire area: 0.3701 sq in per conductor

Conduit internal area: 1.647 sq in

Allowable fill (40%): 0.6588 sq in

Maximum wires: 0.6588 ÷ 0.3701 = 1 wires

Answer: You can fit up to 1 wires of 4/0 AWG THHN in 1-1/4" IMC conduit.