How Many 4/0 AWG Wires Fit in IMC Conduit?
Complete NEC-compliant fill chart for 4/0 AWG THHN wires in Intermediate Metal Conduit (IMC) conduit. Maximum wire counts for all standard conduit sizes.
Quick Answer
For 4/0 AWG THHN wires in IMC conduit at 40% fill (3+ wires):
- • 1" IMC: 1 wires
- • 1-1/4" IMC: 1 wires
- • 1-1/2" IMC: 2 wires
4/0 AWG in IMC Conduit Fill Chart
Conduit Size | Max Wires (40% Fill) | Fill % | Max Wires (Nipple 60%) | Fill % |
---|---|---|---|---|
1" | 1 | 39% | 1 | 39% |
1-1/4" | 1 | 22% | 2 | 45% |
1-1/2" | 2 | 33% | 3 | 50% |
2" | 3 | 30% | 5 | 50% |
2-1/2" | 6 | 35% | 10 | 58% |
3" | 10 | 38% | 15 | 57% |
3-1/2" | 13 | 38% | 20 | 59% |
4" | 17 | 40% | 25 | 58% |
Understanding the Fill Chart
According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:
- 1 conductor: 53% fill maximum
- 2 conductors: 31% fill maximum
- 3 or more conductors: 40% fill maximum
- Nipples (24" or less): 60% fill maximum
This chart shows the maximum number of 4/0 AWG THHN conductors that can fit in each IMC conduit size while maintaining NEC compliance.
Calculation Example
Question: How many 4/0 AWG THHN wires can fit in 1-1/4" IMC conduit?
Wire area: 0.3701 sq in per conductor
Conduit internal area: 1.647 sq in
Allowable fill (40%): 0.6588 sq in
Maximum wires: 0.6588 ÷ 0.3701 = 1 wires
Answer: You can fit up to 1 wires of 4/0 AWG THHN in 1-1/4" IMC conduit.