How Many 6 AWG Wires Fit in PVC Conduit?
Complete NEC-compliant fill chart for 6 AWG THHN wires in Schedule 40 PVC (PVC) conduit. Maximum wire counts for all standard conduit sizes.
Quick Answer
For 6 AWG THHN wires in PVC conduit at 40% fill (3+ wires):
- • 1/2" PVC: 2 wires
- • 3/4" PVC: 4 wires
- • 1" PVC: 6 wires
6 AWG in PVC Conduit Fill Chart
Conduit Size | Max Wires (40% Fill) | Fill % | Max Wires (Nipple 60%) | Fill % |
---|---|---|---|---|
1/2" | 2 | 36% | 3 | 53% |
3/4" | 4 | 40% | 6 | 60% |
1" | 6 | 37% | 9 | 55% |
1-1/4" | 11 | 39% | 16 | 57% |
1-1/2" | 15 | 38% | 23 | 59% |
2" | 25 | 39% | 38 | 59% |
2-1/2" | 43 | 40% | 64 | 60% |
3" | 68 | 40% | 102 | 60% |
3-1/2" | 89 | 40% | 134 | 60% |
4" | 112 | 40% | 169 | 60% |
Understanding the Fill Chart
According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:
- 1 conductor: 53% fill maximum
- 2 conductors: 31% fill maximum
- 3 or more conductors: 40% fill maximum
- Nipples (24" or less): 60% fill maximum
This chart shows the maximum number of 6 AWG THHN conductors that can fit in each PVC conduit size while maintaining NEC compliance.
Calculation Example
Question: How many 6 AWG THHN wires can fit in 3/4" PVC conduit?
Wire area: 0.0507 sq in per conductor
Conduit internal area: 0.508 sq in
Allowable fill (40%): 0.2032 sq in
Maximum wires: 0.2032 ÷ 0.0507 = 4 wires
Answer: You can fit up to 4 wires of 6 AWG THHN in 3/4" PVC conduit.