How Many 4 AWG Wires Fit in RMC Conduit?

Complete NEC-compliant fill chart for 4 AWG THHN wires in Rigid Metal Conduit (RMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 4 AWG THHN wires in RMC conduit at 40% fill (3+ wires):

  • • 1/2" RMC: 1 wires
  • • 3/4" RMC: 2 wires
  • • 1" RMC: 4 wires

4 AWG in RMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 1 26% 2 52%
3/4" 2 30% 3 45%
1" 4 37% 6 56%
1-1/4" 7 38% 11 59%
1-1/2" 10 40% 15 60%
2" 16 39% 24 58%
2-1/2" 29 40% 43 59%
3" 43 40% 64 59%
3-1/2" 56 40% 84 59%
4" 72 40% 108 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 4 AWG THHN conductors that can fit in each RMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 4 AWG THHN wires can fit in 3/4" RMC conduit?

Wire area: 0.0824 sq in per conductor

Conduit internal area: 0.549 sq in

Allowable fill (40%): 0.2196 sq in

Maximum wires: 0.2196 ÷ 0.0824 = 2 wires

Answer: You can fit up to 2 wires of 4 AWG THHN in 3/4" RMC conduit.