How Many 3/0 AWG Wires Fit in FMC Conduit?

Complete NEC-compliant fill chart for 3/0 AWG THHN wires in Flexible Metal Conduit (FMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 3/0 AWG THHN wires in FMC conduit at 40% fill (3+ wires):

  • • 1" FMC: 1 wires
  • • 1-1/4" FMC: 1 wires
  • • 1-1/2" FMC: 2 wires

3/0 AWG in FMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1" 1 37% 1 37%
1-1/4" 1 22% 2 45%
1-1/2" 2 32% 3 48%
2" 4 39% 6 58%
2-1/2" 6 35% 10 58%
3" 10 38% 15 56%
3-1/2" 13 37% 20 58%
4" 17 38% 26 59%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 3/0 AWG THHN conductors that can fit in each FMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 3/0 AWG THHN wires can fit in 1-1/4" FMC conduit?

Wire area: 0.3039 sq in per conductor

Conduit internal area: 1.365 sq in

Allowable fill (40%): 0.5460 sq in

Maximum wires: 0.5460 ÷ 0.3039 = 1 wires

Answer: You can fit up to 1 wires of 3/0 AWG THHN in 1-1/4" FMC conduit.