How Many 8 AWG Wires Fit in EMT Conduit?

Complete NEC-compliant fill chart for 8 AWG THHN wires in Electrical Metallic Tubing (EMT) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 8 AWG THHN wires in EMT conduit at 40% fill (3+ wires):

  • • 1/2" EMT: 3 wires
  • • 3/4" EMT: 5 wires
  • • 1" EMT: 9 wires

8 AWG in EMT Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 3 36% 4 48%
3/4" 5 34% 8 55%
1" 9 38% 14 59%
1-1/4" 16 39% 24 59%
1-1/2" 22 40% 33 59%
2" 36 39% 55 60%
2-1/2" 64 40% 96 60%
3" 96 40% 145 60%
3-1/2" 126 40% 189 60%
4" 161 40% 241 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 8 AWG THHN conductors that can fit in each EMT conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 8 AWG THHN wires can fit in 3/4" EMT conduit?

Wire area: 0.0366 sq in per conductor

Conduit internal area: 0.533 sq in

Allowable fill (40%): 0.2132 sq in

Maximum wires: 0.2132 ÷ 0.0366 = 5 wires

Answer: You can fit up to 5 wires of 8 AWG THHN in 3/4" EMT conduit.