Conduit Sizing for Solar Installations - Complete NEC Guide
Solar photovoltaic installations present unique conduit sizing challenges that differ from traditional electrical work due to specialized wire types, high voltage DC circuits, outdoor exposure requirements, and specific NEC Article 690 regulations governing PV systems. Whether you're installing a residential rooftop system, commercial ground-mount array, or utility-scale solar farm, understanding proper conduit sizing ensures safe, code-compliant installations that protect both the system and personnel. This comprehensive guide covers everything electricians and solar installers need to know about sizing conduit for solar PV systems, from basic requirements through complex multi-string configurations.
Understanding PV Wire and Solar-Specific Conductors
Photovoltaic systems use specialized conductors designed to withstand the unique environmental conditions and electrical characteristics of solar installations. Understanding these wire types is essential for proper conduit sizing.
PV Wire (Photovoltaic Wire) Characteristics
PV wire represents the industry standard conductor for exposed outdoor DC wiring on solar installations. This specialized wire type has specific characteristics:
- Temperature rating: 90°C wet and dry locations (some varieties rated to 150°C in dry)
- Voltage rating: 600V, 1000V, or 2000V depending on specification
- Sunlight resistance: UV-resistant jacket rated for continuous outdoor exposure
- Moisture resistance: Waterproof construction suitable for direct weather exposure
- Flame rating: Passes UL flame tests required for building wire
- Temperature range: Typically rated from -40°C to 90°C or higher
PV wire designation "USE-2" indicates Underground Service Entrance cable, Second generation. This dual-rating allows the wire to be used in conduit, as direct burial cable, or as exposed outdoor wiring (when properly supported). The cross-linked polyethylene (XLPE) insulation provides superior performance compared to standard THHN/THWN.
PV Wire Cross-Sectional Areas
For conduit fill calculations, PV wire dimensions come from NEC Chapter 9, Table 5, under the RHW-2 column (for USE-2/RHW-2 rated wire). Common sizes include:
- 10 AWG USE-2/RHW-2: 0.0333 square inches
- 8 AWG USE-2/RHW-2: 0.0437 square inches
- 6 AWG USE-2/RHW-2: 0.0726 square inches
- 4 AWG USE-2/RHW-2: 0.0973 square inches
Note that PV wire is larger in diameter than THHN/THWN of the same gauge due to thicker insulation required for outdoor service and higher voltage ratings.
Alternative Wire Types for Solar
While PV wire dominates exposed outdoor applications, other wire types serve specific purposes:
THHN/THWN-2 or XHHW-2: Acceptable for PV source circuits when installed in conduit and not exposed to direct sunlight. These standard building wires work well for conduit runs from the array to the combiner box or from combiner to inverter.
USE-2 without PV rating: Suitable for underground service entrance applications but not for exposed outdoor PV wiring. Check markings carefully - not all USE-2 is rated for PV use.
XHHW-2: Cross-linked polyethylene insulation rated 90°C wet, similar properties to PV wire but typically not sunlight resistant without conduit protection.
Outdoor and Wet Location Requirements
Solar installations face environmental exposure that exceeds typical electrical work, requiring special consideration for conduit selection and sizing.
Conduit Materials for Outdoor Solar Applications
Several conduit types suit solar installations, each with specific advantages:
PVC Schedule 40 and Schedule 80: Excellent UV resistance, corrosion immunity, and cost-effectiveness make PVC the most popular choice for solar installations. Schedule 40 works for most underground applications, while Schedule 80 provides additional strength for exposed outdoor runs. PVC resists moisture and temperature extremes better than metal conduits.
Electrical Metallic Tubing (EMT): Lighter weight and easier installation than rigid conduit make EMT suitable for indoor portions of solar wiring. However, EMT requires proper outdoor ratings and protection when used in exposed locations. In many regions, EMT corrodes quickly outdoors unless protected.
Rigid Metal Conduit (RMC): Provides maximum physical protection for exposed outdoor runs where damage risk is high. Hot-dipped galvanized or stainless steel RMC resists corrosion in harsh environments. RMC is often required by AHJs in commercial installations or high-wind zones.
Rigid Nonmetallic Conduit (RNC): HDPE, fiberglass, or PVC conduits rated for direct burial provide excellent durability for underground solar farm applications. These materials resist UV degradation when buried and handle soil chemicals better than metal.
Temperature Derating Considerations
Solar installations face extreme temperature conditions that affect conductor ampacity:
Critical Requirement - NEC 690.7(A):
PV system voltage, current, and power values must be calculated at the lowest expected ambient temperature, which increases voltage and may decrease current. Conversely, ampacity calculations use the highest expected ambient temperature. Rooftop conduit may experience ambient temperatures of 70-75°C (158-167°F) in direct summer sun, requiring significant ampacity derating per NEC 310.15(B)(3)(a) temperature correction factors.
When conduit is exposed to direct sunlight on rooftops, NEC requires using temperature adders (typically +30°C to +40°C above ambient) before applying ampacity corrections. This often necessitates oversized conductors and larger conduits than initial calculations suggest.
Grounding and Bonding Conductor Requirements
Solar PV systems require specific grounding and bonding conductors that must be included in conduit fill calculations.
Equipment Grounding Conductors
NEC 690.43 requires equipment grounding conductors for all metallic equipment and enclosures in PV systems. Size requirements follow NEC 250.122, based on the overcurrent device rating:
- Circuits up to 20A: 12 AWG minimum (10 AWG PV wire often used)
- Circuits 21-30A: 10 AWG minimum
- Circuits 31-60A: 10 AWG copper minimum
- Circuits 61-100A: 8 AWG copper minimum
- Larger circuits: See NEC Table 250.122
Equipment grounding conductors must be counted in conduit fill calculations per NEC Chapter 9, Table 1. Many installers use green-jacketed PV wire for visible equipment grounding to simplify identification.
Grounding Electrode Conductors
NEC 690.47 requires grounding electrode conductors connecting PV system equipment to the grounding electrode system. These conductors typically run from the inverter or combiner box to ground rods, building steel, or other electrodes. When run in conduit with other conductors, they count toward fill calculations.
Module Frame Bonding
PV module frames must be bonded together and to the equipment grounding system. While some systems use dedicated bonding conductors run through conduit, modern installations often rely on listed grounding clamps and rails that provide bonding without additional conductors, reducing conduit fill requirements.
String Inverter vs Microinverter System Wiring
The inverter architecture dramatically affects conduit requirements and sizing calculations.
String Inverter Systems
Traditional string inverter systems connect multiple solar panels in series strings, with DC wiring running from the array to a centralized inverter:
DC source circuits: Each string requires two current-carrying conductors (positive and negative) plus an equipment ground. For a system with three strings, you need 6 current-carrying conductors (3 positive + 3 negative) plus 1 or more grounds. These DC conductors often carry 8-12 amps per string at voltages of 200-600VDC.
DC conductor sizing: NEC 690.8(B) requires PV source circuit conductors to be sized at 156% of the short-circuit current (Isc × 1.56). This safety factor accounts for potential module current increases due to reflective surfaces, cloud enhancement effects, and other irradiance anomalies.
Typical conduit run: From rooftop array penetration to inverter location, typically 20-100 feet. Larger conduit sizes provide easier wire pulling and better heat dissipation.
Microinverter Systems
Microinverter systems place an individual inverter on each solar panel, converting DC to AC at the module level:
AC branch circuits: Microinverters connect to AC branch circuits that parallel multiple units. Instead of high-voltage DC, these systems use standard 240VAC circuits (in North America). Each branch circuit might serve 10-15 microinverters, depending on inverter output ratings.
AC conductor sizing: Standard NEC Article 210 and 215 requirements apply, with 125% continuous load sizing per NEC 690.8(A)(1). A branch circuit supporting fifteen 300W microinverters requires conductors sized for (15 × 300W ÷ 240V) × 1.25 = 23.4 amperes, typically 10 AWG.
Trunk and branch configuration: Microinverter systems use AC trunk cables with branches to individual inverters. The conduit run typically contains one multiwire branch circuit or multiple branch circuits sharing a conduit, from the array to a dedicated PV breaker in the main service panel.
Conduit Sizing Comparison
String inverter systems generally require larger conduit sizes due to:
- Thicker PV wire insulation compared to standard building wire
- Multiple DC circuits bundled together (ampacity derating may force larger wire)
- Higher voltage requirements for longer-distance DC runs
Microinverter systems typically need smaller conduit because:
- AC branch circuits use standard THHN/THWN building wire
- Lower voltage (240VAC vs 400-600VDC) allows smaller conductors for equivalent power
- Shorter individual wire runs reduce voltage drop concerns
Practical Conduit Sizing Examples
Example 1: Residential String Inverter System (5kW)
System Configuration:
- 15 solar panels × 335W = 5.0 kW system
- Configured as 2 strings (8 panels + 7 panels)
- Each string: 8 × 40V = 320VDC approximate
- String current: 8.5A Isc per string
- Distance: Array to inverter = 50 feet through conduit
Wire Sizing Calculation:
Required conductor size: 8.5A × 1.56 = 13.26A
From NEC 310.16, 90°C column: 10 AWG PV wire rated 40A
Temperature correction (60°C ambient): 40A × 0.82 = 32.8A (adequate)
Conductors Required:
- 4 current-carrying: 2 strings × 2 conductors (+ and -)
- 1 equipment ground: 10 AWG
- Total: 5 conductors × 10 AWG USE-2/RHW-2
Conduit Calculation:
10 AWG USE-2/RHW-2 area: 0.0333 sq in (from Table 5)
Total conductor area: 5 × 0.0333 = 0.1665 sq in
Required conduit area at 40%: 0.1665 ÷ 0.40 = 0.4163 sq in
3/4" PVC Schedule 40 (0.533 sq in) is adequate
Recommendation: Use 1" PVC Schedule 40 for easier pulling and future expansion capability, especially considering the 50-foot run.
Example 2: Commercial String Inverter System (25kW)
System Configuration:
- 75 panels × 335W = 25.1 kW system
- Configured as 5 strings of 15 panels each
- String voltage: 15 × 40V = 600VDC
- String current: 8.5A Isc per string
- Distance: 80 feet from array to inverter room
Wire Sizing Calculation:
Required conductor size: 8.5A × 1.56 = 13.26A per string
Use 10 AWG PV wire (USE-2/RHW-2) for each string
Conductors Required:
- 10 current-carrying: 5 strings × 2 conductors
- 1 equipment ground: 8 AWG (for 30A overcurrent)
- Total: (10 × 10 AWG) + (1 × 8 AWG) in USE-2/RHW-2
Ampacity Derating:
10 current-carrying conductors require 50% derating (NEC 310.15(C)(1))
10 AWG 90°C rating: 40A × 0.50 = 20A
Temperature correction (65°C): 20A × 0.76 = 15.2A
15.2A > 13.26A required - wire size is adequate
Conduit Calculation:
10 AWG USE-2 area: 0.0333 sq in × 10 conductors = 0.3330 sq in
8 AWG USE-2 area: 0.0437 sq in × 1 conductor = 0.0437 sq in
Total area: 0.3767 sq in
Required at 40%: 0.3767 ÷ 0.40 = 0.9418 sq in
1-1/4" PVC Sch 40 (1.195 sq in) is adequate
Recommendation: Use 1-1/2" PVC Schedule 40 for this application. The additional space eases installation with 11 conductors over 80 feet and provides thermal relief for bundled conductors.
Example 3: Residential Microinverter System (6kW)
System Configuration:
- 18 panels × 335W = 6.0 kW system
- 18 microinverters at 300W AC output each
- Two AC branch circuits (9 inverters per circuit)
- Distance: 40 feet from array to main panel
Wire Sizing Calculation:
Per circuit: 9 × 300W ÷ 240V = 11.25A
Continuous load sizing: 11.25A × 1.25 = 14.1A
Use 12 AWG THWN-2 (20A rating adequate)
Conductors Required:
- Circuit 1: 2 hots + 1 neutral (if needed) + 1 ground = 4 conductors
- Circuit 2: 2 hots + 1 neutral (if needed) + 1 ground = 4 conductors
- Total: 8 × 12 AWG THWN-2 (or 6 if shared neutral/ground permitted)
Conduit Calculation:
12 AWG THWN-2 area: 0.0133 sq in
Total area: 8 × 0.0133 = 0.1064 sq in
Required at 40%: 0.1064 ÷ 0.40 = 0.2660 sq in
1/2" EMT (0.304 sq in) is adequate
Recommendation: Use 3/4" EMT for ease of pulling and to accommodate possible future additional circuits. Microinverter systems typically require smaller conduit than equivalent string inverter systems.
NEC Article 690 Specific Requirements
NEC Article 690 contains comprehensive requirements for solar photovoltaic systems that directly impact conduit sizing and installation.
Key Article 690 Provisions
NEC 690.8 - Circuit Sizing and Current
- 690.8(A)(1): AC PV system output circuits sized at 125% of continuous current
- 690.8(B)(1): DC PV source circuits sized at 156% of short-circuit current
- 690.8(B)(2): DC PV output circuits sized at 125% of maximum current
These safety factors ensure conductors can handle maximum potential currents including edge-of-cloud enhancement and other irradiance anomalies that can temporarily exceed standard test conditions.
Temperature Correction Requirements
NEC 690.7 requires calculating voltage, current, and power at lowest expected ambient temperature for voltage calculations and highest expected ambient temperature for ampacity calculations. For conduit sizing, focus on the ampacity requirements:
- Determine maximum expected ambient temperature (often 40°C/104°F or higher)
- Add temperature adder for rooftop conduit exposure (+30-40°C)
- Apply correction factors from NEC 310.15(B)(2)(a)
- Apply adjustment factors for conductor bundling from 310.15(B)(3)(a)
- Verify final ampacity exceeds 156% of Isc (for DC circuits)
Conduit Fill and Ampacity Derating Interaction
More conductors in a conduit require larger wire sizes due to ampacity derating, which then affects conduit fill calculations. This iterative process requires:
- Calculate minimum wire size based on current requirements
- Determine number of current-carrying conductors
- Apply ampacity adjustment factor based on conductor count
- If adjusted ampacity is insufficient, increase wire size
- Recalculate conduit fill with larger wire size
- Verify conduit size accommodates all conductors at proper fill percentage
Residential vs Commercial Solar Installation Differences
Residential Systems (2-10 kW typical)
- System size: Usually 8-20 solar panels, 1-3 strings for string inverters
- Conduit runs: Typically 20-60 feet from roof penetration to inverter location
- Common wire sizes: 10 AWG or 12 AWG for most applications
- Typical conduit: 3/4" to 1" PVC or EMT
- Complexity: Relatively straightforward calculations with limited conductor counts
- Microinverters: Very popular for residential, simplifying DC wiring
Commercial Systems (25-500 kW typical)
- System size: 75-1500+ panels, multiple parallel strings
- Conduit runs: Can exceed 200 feet from array to inverter room or utility connection
- Common wire sizes: Range from 10 AWG (source circuits) to 500 kcmil (utility interconnection)
- Typical conduit: 1-1/4" to 4" PVC, EMT, or RMC depending on application
- Complexity: Multiple combiner boxes, parallel string homerun, complex ampacity derating
- String inverters: Dominant architecture for commercial scale
Best Practices and Professional Tips
Installation Best Practices:
- Size up: Always consider one size larger conduit than minimum calculation suggests
- Future expansion: Solar systems often expand - oversized conduit accommodates additions
- Pull string: Install pull string in all conduit for future reuse or additional circuits
- Continuous conduit: Minimize splices and fittings that increase pulling difficulty
- Support properly: Follow NEC 352 for PVC support requirements (every 3 feet vertical, every 10 feet horizontal maximum)
- Label clearly: Mark all conduits with "PHOTOVOLTAIC POWER SOURCE" per NEC 690.31(E)
Documentation and Inspection
Maintain comprehensive documentation for every solar installation:
- Conduit fill calculations with all conductors identified
- Wire size calculations including all safety factors and corrections
- Single-line diagrams showing all circuits and conduit routes
- Manufacturer specifications for all wire and conduit materials
- As-built drawings reflecting actual installation (critical for future service)
Common Mistakes to Avoid
1. Forgetting Temperature Corrections
Rooftop conduit can reach 70-75°C in summer sun. Failing to apply temperature correction factors results in undersized conductors that may overheat, causing system failures or fire hazards.
2. Incorrect Current Calculations
Using module rated current instead of short-circuit current (Isc), or forgetting the 1.56 multiplier for PV source circuits, leads to undersized conductors. Always use Isc × 1.56 for DC source circuit sizing.
3. Using Wrong Wire Type
Installing THHN/THWN in exposed outdoor locations without conduit protection violates code and causes premature failure. Use properly rated PV wire (USE-2/RHW-2 with PV rating) for all exposed outdoor applications.
4. Inadequate Conduit Size
Calculating minimum conduit size without considering installation difficulty leads to damaged wire during pulling. Long runs or multiple bends require oversized conduit even when fill calculations show smaller sizes are code-compliant.
5. Not Counting Equipment Grounds
Equipment grounding conductors must be included in fill calculations. This oversight results in overfilled conduit that may fail inspection or require costly rework.
Tools and Resources
- Conduit Fill Calculator - Size conduit for solar power circuits
- NEC Article 690: Complete code requirements for PV systems
- Solar module datasheets: Provide Isc, Voc, and temperature coefficients
- Inverter specifications: Maximum input current and voltage requirements
- Wire manufacturer catalogs: Exact PV wire dimensions and specifications
Conclusion
Proper conduit sizing for solar photovoltaic installations requires understanding specialized PV wire characteristics, applying NEC Article 690 requirements, accounting for extreme outdoor temperature conditions, sizing for appropriate safety factors, and choosing conduit materials suitable for long-term outdoor exposure. Whether installing residential microinverter systems or large commercial string inverter arrays, careful attention to these requirements ensures safe, code-compliant installations that protect equipment and personnel while maintaining system performance over decades of operation.
Remember that solar conduit sizing differs significantly from traditional electrical work - the combination of DC circuits, outdoor exposure, temperature extremes, and specialized wire types creates unique challenges. Always apply the 156% factor for PV source circuits, use proper temperature corrections for rooftop installations, count all conductors including equipment grounds in fill calculations, and select conduit materials rated for continuous outdoor exposure. When in doubt, size up - the marginal cost of larger conduit is minimal compared to the expense and disruption of replacing undersized pathways after installation.