How Many 2/0 AWG Wires Fit in EMT Conduit?

Complete NEC-compliant fill chart for 2/0 AWG THHN wires in Electrical Metallic Tubing (EMT) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 2/0 AWG THHN wires in EMT conduit at 40% fill (3+ wires):

  • • 1" EMT: 1 wires
  • • 1-1/4" EMT: 2 wires
  • • 1-1/2" EMT: 3 wires

2/0 AWG in EMT Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1" 1 26% 2 51%
1-1/4" 2 30% 4 59%
1-1/2" 3 33% 5 55%
2" 6 40% 9 60%
2-1/2" 10 38% 15 57%
3" 15 38% 23 58%
3-1/2" 20 39% 31 60%
4" 26 39% 39 59%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 2/0 AWG THHN conductors that can fit in each EMT conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 2/0 AWG THHN wires can fit in 1-1/4" EMT conduit?

Wire area: 0.2223 sq in per conductor

Conduit internal area: 1.496 sq in

Allowable fill (40%): 0.5984 sq in

Maximum wires: 0.5984 ÷ 0.2223 = 2 wires

Answer: You can fit up to 2 wires of 2/0 AWG THHN in 1-1/4" EMT conduit.