How Many 1 AWG Wires Fit in IMC Conduit?

Complete NEC-compliant fill chart for 1 AWG THHN wires in Intermediate Metal Conduit (IMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 1 AWG THHN wires in IMC conduit at 40% fill (3+ wires):

  • • 3/4" IMC: 1 wires
  • • 1" IMC: 2 wires
  • • 1-1/4" IMC: 4 wires

1 AWG in IMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
3/4" 1 27% 2 53%
1" 2 33% 3 49%
1-1/4" 4 38% 6 57%
1-1/2" 5 35% 8 56%
2" 9 38% 14 60%
2-1/2" 16 39% 24 59%
3" 24 39% 37 60%
3-1/2" 32 40% 48 60%
4" 40 39% 61 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 1 AWG THHN conductors that can fit in each IMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 1 AWG THHN wires can fit in 1" IMC conduit?

Wire area: 0.1562 sq in per conductor

Conduit internal area: 0.959 sq in

Allowable fill (40%): 0.3836 sq in

Maximum wires: 0.3836 ÷ 0.1562 = 2 wires

Answer: You can fit up to 2 wires of 1 AWG THHN in 1" IMC conduit.