How Many 6 AWG Wires Fit in RMC Conduit?

Complete NEC-compliant fill chart for 6 AWG THHN wires in Rigid Metal Conduit (RMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 6 AWG THHN wires in RMC conduit at 40% fill (3+ wires):

  • • 1/2" RMC: 2 wires
  • • 3/4" RMC: 4 wires
  • • 1" RMC: 6 wires

6 AWG in RMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 2 32% 3 48%
3/4" 4 37% 6 55%
1" 6 34% 10 57%
1-1/4" 12 40% 18 60%
1-1/2" 16 39% 24 59%
2" 26 39% 40 60%
2-1/2" 47 40% 71 60%
3" 70 40% 105 60%
3-1/2" 92 40% 138 60%
4" 117 40% 176 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 6 AWG THHN conductors that can fit in each RMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 6 AWG THHN wires can fit in 3/4" RMC conduit?

Wire area: 0.0507 sq in per conductor

Conduit internal area: 0.549 sq in

Allowable fill (40%): 0.2196 sq in

Maximum wires: 0.2196 ÷ 0.0507 = 4 wires

Answer: You can fit up to 4 wires of 6 AWG THHN in 3/4" RMC conduit.