How Many 4 AWG Wires Fit in EMT Conduit?
Complete NEC-compliant fill chart for 4 AWG THHN wires in Electrical Metallic Tubing (EMT) conduit. Maximum wire counts for all standard conduit sizes.
Quick Answer
For 4 AWG THHN wires in EMT conduit at 40% fill (3+ wires):
- • 1/2" EMT: 1 wires
- • 3/4" EMT: 2 wires
- • 1" EMT: 4 wires
4 AWG in EMT Conduit Fill Chart
Conduit Size | Max Wires (40% Fill) | Fill % | Max Wires (Nipple 60%) | Fill % |
---|---|---|---|---|
1/2" | 1 | 27% | 2 | 54% |
3/4" | 2 | 31% | 3 | 46% |
1" | 4 | 38% | 6 | 57% |
1-1/4" | 7 | 39% | 10 | 55% |
1-1/2" | 9 | 36% | 14 | 57% |
2" | 16 | 39% | 24 | 59% |
2-1/2" | 28 | 39% | 42 | 59% |
3" | 42 | 39% | 64 | 60% |
3-1/2" | 56 | 40% | 84 | 60% |
4" | 71 | 40% | 107 | 60% |
Understanding the Fill Chart
According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:
- 1 conductor: 53% fill maximum
- 2 conductors: 31% fill maximum
- 3 or more conductors: 40% fill maximum
- Nipples (24" or less): 60% fill maximum
This chart shows the maximum number of 4 AWG THHN conductors that can fit in each EMT conduit size while maintaining NEC compliance.
Calculation Example
Question: How many 4 AWG THHN wires can fit in 3/4" EMT conduit?
Wire area: 0.0824 sq in per conductor
Conduit internal area: 0.533 sq in
Allowable fill (40%): 0.2132 sq in
Maximum wires: 0.2132 ÷ 0.0824 = 2 wires
Answer: You can fit up to 2 wires of 4 AWG THHN in 3/4" EMT conduit.