How Many 3/0 AWG Wires Fit in IMC Conduit?

Complete NEC-compliant fill chart for 3/0 AWG THHN wires in Intermediate Metal Conduit (IMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 3/0 AWG THHN wires in IMC conduit at 40% fill (3+ wires):

  • • 1" IMC: 1 wires
  • • 1-1/4" IMC: 2 wires
  • • 1-1/2" IMC: 2 wires

3/0 AWG in IMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1" 1 32% 1 32%
1-1/4" 2 37% 3 55%
1-1/2" 2 27% 4 55%
2" 4 33% 7 58%
2-1/2" 8 38% 12 57%
3" 12 38% 19 60%
3-1/2" 16 39% 24 58%
4" 20 38% 31 59%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 3/0 AWG THHN conductors that can fit in each IMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 3/0 AWG THHN wires can fit in 1-1/4" IMC conduit?

Wire area: 0.3039 sq in per conductor

Conduit internal area: 1.647 sq in

Allowable fill (40%): 0.6588 sq in

Maximum wires: 0.6588 ÷ 0.3039 = 2 wires

Answer: You can fit up to 2 wires of 3/0 AWG THHN in 1-1/4" IMC conduit.