How Many 300 MCM Wires Fit in RMC Conduit?
Complete NEC-compliant fill chart for 300 MCM THHN wires in Rigid Metal Conduit (RMC) conduit. Maximum wire counts for all standard conduit sizes.
Quick Answer
Maximum 300 kcmil THHN conductors in RMC conduit under NEC Chapter 9, Table 1 (40% for 3 or more, 31% for 2, 53% for 1):
- • 1-1/4" RMC: 1 wire (53% limit for 1)
- • 1-1/2" RMC: 1 wire (53% limit for 1)
- • 2" RMC: 3 wires
300 kcmil in RMC Conduit Fill Chart
| Conduit Size | Max Wires (Table 1) | Fill % | Max Wires (Nipple 60%) | Fill % | Calculator |
|---|---|---|---|---|---|
| 1-1/4" | 1 (53%) | 30.2% | 2 | 60.4% | Open |
| 1-1/2" | 1 (53%) | 22.3% | 2 | 44.5% | Open |
| 2" | 3 | 40.6% | 4 | 54.1% | Open |
| 2-1/2" | 4 | 37.9% | 6 | 56.8% | Open |
| 3" | 6 | 36.9% | 9 | 55.3% | Open |
| 3-1/2" | 8 | 36.8% | 13 | 59.8% | Open |
| 4" | 11 | 39.3% | 16 | 57.2% | Open |
Areas: NEC Chapter 9 Table 4 (RMC) and Table 5 (THHN 300 kcmil = 0.4608 sq in), recomputed with this site's calculator data on October 31, 2026. All counts include Chapter 9 Note 7 (round up when the division ends in 0.8 or more), the same rule the calculator applies, so a fill shown slightly above the limit can still be allowed. A count in brackets uses the 31% or 53% limit for two or one conductor. Nipples are 24 inches or shorter.
Understanding the Fill Chart
According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:
- 1 conductor: 53% fill maximum
- 2 conductors: 31% fill maximum
- 3 or more conductors: 40% fill maximum
- Nipples (24" or less): 60% fill maximum
This chart shows the maximum number of 300 MCM THHN conductors that can fit in each RMC conduit size while maintaining NEC compliance.
Calculation Example
Question: How many 300 kcmil THHN wires can fit in 2" RMC conduit?
Wire area: 0.4608 sq in per conductor
Conduit internal area: 3.408 sq in
Allowable fill (40%): 1.3632 sq in
Maximum wires: 1.3632 ÷ 0.4608 = 2.96 → 3 wires (Note 7: decimal ≥ 0.8 rounds up)
Answer: You can fit up to 3 wires of 300 kcmil THHN in 2" RMC conduit (40.6% fill). Check it in the calculator.