How Many 10 AWG Wires Fit in RMC Conduit?

Complete NEC-compliant fill chart for 10 AWG THHN wires in Rigid Metal Conduit (RMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 10 AWG THHN wires in RMC conduit at 40% fill (3+ wires):

  • • 1/2" RMC: 5 wires
  • • 3/4" RMC: 10 wires
  • • 1" RMC: 16 wires

10 AWG in RMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 5 34% 8 54%
3/4" 10 38% 15 58%
1" 16 38% 25 59%
1-1/4" 28 39% 43 59%
1-1/2" 39 40% 58 59%
2" 64 40% 96 59%
2-1/2" 113 40% 170 60%
3" 169 40% 253 60%
3-1/2" 221 40% 331 60%
4" 282 40% 423 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 10 AWG THHN conductors that can fit in each RMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 10 AWG THHN wires can fit in 3/4" RMC conduit?

Wire area: 0.0211 sq in per conductor

Conduit internal area: 0.549 sq in

Allowable fill (40%): 0.2196 sq in

Maximum wires: 0.2196 ÷ 0.0211 = 10 wires

Answer: You can fit up to 10 wires of 10 AWG THHN in 3/4" RMC conduit.