How Many 2/0 AWG Wires Fit in IMC Conduit?

Complete NEC-compliant fill chart for 2/0 AWG THHN wires in Intermediate Metal Conduit (IMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 2/0 AWG THHN wires in IMC conduit at 40% fill (3+ wires):

  • • 3/4" IMC: 1 wires
  • • 1" IMC: 1 wires
  • • 1-1/4" IMC: 2 wires

2/0 AWG in IMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
3/4" 1 38% 1 38%
1" 1 23% 2 46%
1-1/4" 2 27% 4 54%
1-1/2" 4 40% 6 60%
2" 6 36% 9 55%
2-1/2" 11 38% 17 59%
3" 17 39% 26 60%
3-1/2" 22 39% 33 58%
4" 28 39% 42 59%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 2/0 AWG THHN conductors that can fit in each IMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 2/0 AWG THHN wires can fit in 1" IMC conduit?

Wire area: 0.2223 sq in per conductor

Conduit internal area: 0.959 sq in

Allowable fill (40%): 0.3836 sq in

Maximum wires: 0.3836 ÷ 0.2223 = 1 wires

Answer: You can fit up to 1 wires of 2/0 AWG THHN in 1" IMC conduit.