How Many 14 AWG Wires Fit in PVC Conduit?

Complete NEC-compliant fill chart for 14 AWG THHN wires in Schedule 40 PVC (PVC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 14 AWG THHN wires in PVC conduit at 40% fill (3+ wires):

  • • 1/2" PVC: 11 wires
  • • 3/4" PVC: 20 wires
  • • 1" PVC: 34 wires

14 AWG in PVC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 11 37% 17 58%
3/4" 20 38% 31 59%
1" 34 40% 51 59%
1-1/4" 58 39% 88 60%
1-1/2" 81 40% 122 60%
2" 135 40% 203 60%
2-1/2" 224 40% 337 60%
3" 358 40% 537 60%
3-1/2" 468 40% 702 60%
4" 590 40% 885 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 14 AWG THHN conductors that can fit in each PVC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 14 AWG THHN wires can fit in 3/4" PVC conduit?

Wire area: 0.0097 sq in per conductor

Conduit internal area: 0.508 sq in

Allowable fill (40%): 0.2032 sq in

Maximum wires: 0.2032 ÷ 0.0097 = 20 wires

Answer: You can fit up to 20 wires of 14 AWG THHN in 3/4" PVC conduit.