How Many 12 AWG Wires Fit in FMC Conduit?

Complete NEC-compliant fill chart for 12 AWG THHN wires in Flexible Metal Conduit (FMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 12 AWG THHN wires in FMC conduit at 40% fill (3+ wires):

  • • 1/2" FMC: 9 wires
  • • 3/4" FMC: 15 wires
  • • 1" FMC: 24 wires

12 AWG in FMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 9 40% 13 57%
3/4" 15 39% 22 58%
1" 24 39% 36 59%
1-1/4" 41 40% 61 59%
1-1/2" 57 40% 85 59%
2" 94 40% 141 60%
2-1/2" 158 40% 237 60%
3" 243 40% 364 60%
3-1/2" 317 40% 476 60%
4" 403 40% 605 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 12 AWG THHN conductors that can fit in each FMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 12 AWG THHN wires can fit in 3/4" FMC conduit?

Wire area: 0.0133 sq in per conductor

Conduit internal area: 0.508 sq in

Allowable fill (40%): 0.2032 sq in

Maximum wires: 0.2032 ÷ 0.0133 = 15 wires

Answer: You can fit up to 15 wires of 12 AWG THHN in 3/4" FMC conduit.

Related Tools