How Many 10 AWG Wires Fit in IMC Conduit?

Complete NEC-compliant fill chart for 10 AWG THHN wires in Intermediate Metal Conduit (IMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 10 AWG THHN wires in IMC conduit at 40% fill (3+ wires):

  • • 1/2" IMC: 6 wires
  • • 3/4" IMC: 11 wires
  • • 1" IMC: 18 wires

10 AWG in IMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 6 37% 9 56%
3/4" 11 40% 16 58%
1" 18 40% 27 59%
1-1/4" 31 40% 46 59%
1-1/2" 42 40% 63 60%
2" 69 40% 104 60%
2-1/2" 121 40% 182 60%
3" 183 40% 275 60%
3-1/2" 237 40% 356 60%
4" 301 40% 452 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 10 AWG THHN conductors that can fit in each IMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 10 AWG THHN wires can fit in 3/4" IMC conduit?

Wire area: 0.0211 sq in per conductor

Conduit internal area: 0.586 sq in

Allowable fill (40%): 0.2344 sq in

Maximum wires: 0.2344 ÷ 0.0211 = 11 wires

Answer: You can fit up to 11 wires of 10 AWG THHN in 3/4" IMC conduit.