How Many 6 AWG Wires Fit in FMC Conduit?

Complete NEC-compliant fill chart for 6 AWG THHN wires in Flexible Metal Conduit (FMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 6 AWG THHN wires in FMC conduit at 40% fill (3+ wires):

  • • 1/2" FMC: 2 wires
  • • 3/4" FMC: 4 wires
  • • 1" FMC: 6 wires

6 AWG in FMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 2 34% 3 51%
3/4" 4 40% 6 60%
1" 6 37% 9 56%
1-1/4" 10 37% 16 59%
1-1/2" 14 37% 22 59%
2" 24 39% 37 60%
2-1/2" 41 40% 62 60%
3" 63 39% 95 60%
3-1/2" 83 40% 125 60%
4" 105 40% 158 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 6 AWG THHN conductors that can fit in each FMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 6 AWG THHN wires can fit in 3/4" FMC conduit?

Wire area: 0.0507 sq in per conductor

Conduit internal area: 0.508 sq in

Allowable fill (40%): 0.2032 sq in

Maximum wires: 0.2032 ÷ 0.0507 = 4 wires

Answer: You can fit up to 4 wires of 6 AWG THHN in 3/4" FMC conduit.