How Many 4/0 AWG Wires Fit in EMT Conduit?

Complete NEC-compliant fill chart for 4/0 AWG THHN wires in Electrical Metallic Tubing (EMT) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 4/0 AWG THHN wires in EMT conduit at 40% fill (3+ wires):

  • • 1-1/4" EMT: 1 wires
  • • 1-1/2" EMT: 2 wires
  • • 2" EMT: 3 wires

4/0 AWG in EMT Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1-1/4" 1 25% 2 49%
1-1/2" 2 36% 3 55%
2" 3 33% 5 55%
2-1/2" 6 38% 9 57%
3" 9 38% 14 59%
3-1/2" 12 38% 18 58%
4" 15 38% 23 58%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 4/0 AWG THHN conductors that can fit in each EMT conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 4/0 AWG THHN wires can fit in 1-1/2" EMT conduit?

Wire area: 0.3701 sq in per conductor

Conduit internal area: 2.036 sq in

Allowable fill (40%): 0.8144 sq in

Maximum wires: 0.8144 ÷ 0.3701 = 2 wires

Answer: You can fit up to 2 wires of 4/0 AWG THHN in 1-1/2" EMT conduit.