How Many 2 AWG Wires Fit in IMC Conduit?

Complete NEC-compliant fill chart for 2 AWG THHN wires in Intermediate Metal Conduit (IMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 2 AWG THHN wires in IMC conduit at 40% fill (3+ wires):

  • • 1/2" IMC: 1 wires
  • • 3/4" IMC: 2 wires
  • • 1" IMC: 3 wires

2 AWG in IMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 1 34% 1 34%
3/4" 2 40% 3 59%
1" 3 36% 4 48%
1-1/4" 5 35% 8 56%
1-1/2" 7 36% 11 57%
2" 12 38% 19 60%
2-1/2" 22 40% 33 60%
3" 33 39% 50 60%
3-1/2" 43 40% 65 60%
4" 54 39% 82 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 2 AWG THHN conductors that can fit in each IMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 2 AWG THHN wires can fit in 3/4" IMC conduit?

Wire area: 0.1158 sq in per conductor

Conduit internal area: 0.586 sq in

Allowable fill (40%): 0.2344 sq in

Maximum wires: 0.2344 ÷ 0.1158 = 2 wires

Answer: You can fit up to 2 wires of 2 AWG THHN in 3/4" IMC conduit.