How Many 12 AWG Wires Fit in IMC Conduit?

Complete NEC-compliant fill chart for 12 AWG THHN wires in Intermediate Metal Conduit (IMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 12 AWG THHN wires in IMC conduit at 40% fill (3+ wires):

  • • 1/2" IMC: 10 wires
  • • 3/4" IMC: 17 wires
  • • 1" IMC: 28 wires

12 AWG in IMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 10 39% 15 58%
3/4" 17 39% 26 59%
1" 28 39% 43 60%
1-1/4" 49 40% 74 60%
1-1/2" 66 39% 100 60%
2" 110 40% 165 60%
2-1/2" 192 40% 288 60%
3" 291 40% 437 60%
3-1/2" 377 40% 566 60%
4" 478 40% 717 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 12 AWG THHN conductors that can fit in each IMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 12 AWG THHN wires can fit in 3/4" IMC conduit?

Wire area: 0.0133 sq in per conductor

Conduit internal area: 0.586 sq in

Allowable fill (40%): 0.2344 sq in

Maximum wires: 0.2344 ÷ 0.0133 = 17 wires

Answer: You can fit up to 17 wires of 12 AWG THHN in 3/4" IMC conduit.