How Many 1 AWG Wires Fit in FMC Conduit?

Complete NEC-compliant fill chart for 1 AWG THHN wires in Flexible Metal Conduit (FMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 1 AWG THHN wires in FMC conduit at 40% fill (3+ wires):

  • • 3/4" FMC: 1 wires
  • • 1" FMC: 2 wires
  • • 1-1/4" FMC: 3 wires

1 AWG in FMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
3/4" 1 31% 1 31%
1" 2 38% 3 57%
1-1/4" 3 34% 5 57%
1-1/2" 4 33% 7 58%
2" 8 40% 12 60%
2-1/2" 13 39% 20 59%
3" 20 39% 31 60%
3-1/2" 27 40% 40 59%
4" 34 40% 51 59%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 1 AWG THHN conductors that can fit in each FMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 1 AWG THHN wires can fit in 1" FMC conduit?

Wire area: 0.1562 sq in per conductor

Conduit internal area: 0.817 sq in

Allowable fill (40%): 0.3268 sq in

Maximum wires: 0.3268 ÷ 0.1562 = 2 wires

Answer: You can fit up to 2 wires of 1 AWG THHN in 1" FMC conduit.