How Many 4 AWG Wires Fit in PVC Conduit?

Complete NEC-compliant fill chart for 4 AWG THHN wires in Schedule 40 PVC (PVC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 4 AWG THHN wires in PVC conduit at 40% fill (3+ wires):

  • • 1/2" PVC: 1 wires
  • • 3/4" PVC: 2 wires
  • • 1" PVC: 4 wires

4 AWG in PVC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 1 29% 2 58%
3/4" 2 32% 3 49%
1" 4 40% 6 59%
1-1/4" 6 35% 10 58%
1-1/2" 9 37% 14 58%
2" 15 38% 23 58%
2-1/2" 26 39% 39 59%
3" 42 40% 63 60%
3-1/2" 55 40% 82 59%
4" 69 40% 104 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 4 AWG THHN conductors that can fit in each PVC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 4 AWG THHN wires can fit in 3/4" PVC conduit?

Wire area: 0.0824 sq in per conductor

Conduit internal area: 0.508 sq in

Allowable fill (40%): 0.2032 sq in

Maximum wires: 0.2032 ÷ 0.0824 = 2 wires

Answer: You can fit up to 2 wires of 4 AWG THHN in 3/4" PVC conduit.