How Many 400 MCM Wires Fit in IMC Conduit?
Complete NEC-compliant fill chart for 400 MCM THHN wires in Intermediate Metal Conduit (IMC) conduit. Maximum wire counts for all standard conduit sizes.
Quick Answer
Maximum 400 kcmil THHN conductors in IMC conduit under NEC Chapter 9, Table 1 (40% for 3 or more, 31% for 2, 53% for 1):
- • 1-1/4" IMC: 1 wire (53% limit for 1)
- • 1-1/2" IMC: 1 wire (53% limit for 1)
- • 2" IMC: 2 wires (31% limit for 2)
400 kcmil in IMC Conduit Fill Chart
| Conduit Size | Max Wires (Table 1) | Fill % | Max Wires (Nipple 60%) | Fill % | Calculator |
|---|---|---|---|---|---|
| 1-1/4" | 1 (53%) | 35.6% | 1 | 35.6% | Open |
| 1-1/2" | 1 (53%) | 26.4% | 2 | 52.7% | Open |
| 2" | 2 (31%) | 32.3% | 3 | 48.5% | Open |
| 2-1/2" | 3 | 34.3% | 5 | 57.1% | Open |
| 3" | 5 | 37.0% | 8 | 59.2% | Open |
| 3-1/2" | 7 | 38.8% | 11 | 60.9% | Open |
| 4" | 9 | 38.7% | 14 | 60.2% | Open |
Areas: NEC Chapter 9 Table 4 (IMC) and Table 5 (THHN 400 kcmil = 0.5863 sq in), recomputed with this site's calculator data on October 31, 2026. All counts include Chapter 9 Note 7 (round up when the division ends in 0.8 or more), the same rule the calculator applies, so a fill shown slightly above the limit can still be allowed. A count in brackets uses the 31% or 53% limit for two or one conductor. Nipples are 24 inches or shorter.
Understanding the Fill Chart
According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:
- 1 conductor: 53% fill maximum
- 2 conductors: 31% fill maximum
- 3 or more conductors: 40% fill maximum
- Nipples (24" or less): 60% fill maximum
This chart shows the maximum number of 400 MCM THHN conductors that can fit in each IMC conduit size while maintaining NEC compliance.
Calculation Example
Question: How many 400 kcmil THHN wires can fit in 2" IMC conduit?
Wire area: 0.5863 sq in per conductor
Conduit internal area: 3.63 sq in
Allowable fill (31%): 1.1253 sq in
40% check: 1.4520 ÷ 0.5863 = 2.48 → fewer than 3 conductors, so Table 1 uses 31%: 1.1253 ÷ 0.5863 = 1.92 → 2 wires (Note 7: decimal ≥ 0.8 rounds up)
Answer: You can fit up to 2 wires of 400 kcmil THHN in 2" IMC conduit (32.3% fill). Check it in the calculator.