How Many 6 AWG Wires Fit in IMC Conduit?

Complete NEC-compliant fill chart for 6 AWG THHN wires in Intermediate Metal Conduit (IMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 6 AWG THHN wires in IMC conduit at 40% fill (3+ wires):

  • • 1/2" IMC: 2 wires
  • • 3/4" IMC: 4 wires
  • • 1" IMC: 7 wires

6 AWG in IMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 2 30% 4 59%
3/4" 4 35% 6 52%
1" 7 37% 11 58%
1-1/4" 12 37% 19 58%
1-1/2" 17 39% 26 59%
2" 28 39% 43 59%
2-1/2" 50 40% 75 59%
3" 76 40% 114 60%
3-1/2" 99 40% 148 60%
4" 125 40% 188 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 6 AWG THHN conductors that can fit in each IMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 6 AWG THHN wires can fit in 3/4" IMC conduit?

Wire area: 0.0507 sq in per conductor

Conduit internal area: 0.586 sq in

Allowable fill (40%): 0.2344 sq in

Maximum wires: 0.2344 ÷ 0.0507 = 4 wires

Answer: You can fit up to 4 wires of 6 AWG THHN in 3/4" IMC conduit.