How Many 10 AWG Wires Fit in EMT Conduit?

Complete NEC-compliant fill chart for 10 AWG THHN wires in Electrical Metallic Tubing (EMT) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 10 AWG THHN wires in EMT conduit at 40% fill (3+ wires):

  • • 1/2" EMT: 5 wires
  • • 3/4" EMT: 10 wires
  • • 1" EMT: 16 wires

10 AWG in EMT Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 5 35% 8 56%
3/4" 10 40% 15 59%
1" 16 39% 24 59%
1-1/4" 28 39% 42 59%
1-1/2" 38 39% 57 59%
2" 63 40% 95 60%
2-1/2" 111 40% 166 60%
3" 167 40% 251 60%
3-1/2" 218 40% 328 60%
4" 279 40% 419 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 10 AWG THHN conductors that can fit in each EMT conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 10 AWG THHN wires can fit in 3/4" EMT conduit?

Wire area: 0.0211 sq in per conductor

Conduit internal area: 0.533 sq in

Allowable fill (40%): 0.2132 sq in

Maximum wires: 0.2132 ÷ 0.0211 = 10 wires

Answer: You can fit up to 10 wires of 10 AWG THHN in 3/4" EMT conduit.