How Many 3/0 AWG Wires Fit in RMC Conduit?

Complete NEC-compliant fill chart for 3/0 AWG THHN wires in Rigid Metal Conduit (RMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 3/0 AWG THHN wires in RMC conduit at 40% fill (3+ wires):

  • • 1" RMC: 1 wires
  • • 1-1/4" RMC: 2 wires
  • • 1-1/2" RMC: 2 wires

3/0 AWG in RMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1" 1 34% 1 34%
1-1/4" 2 40% 3 60%
1-1/2" 2 29% 4 59%
2" 4 36% 6 54%
2-1/2" 7 35% 11 56%
3" 11 37% 17 58%
3-1/2" 15 39% 23 60%
4" 19 39% 29 59%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 3/0 AWG THHN conductors that can fit in each RMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 3/0 AWG THHN wires can fit in 1-1/4" RMC conduit?

Wire area: 0.3039 sq in per conductor

Conduit internal area: 1.526 sq in

Allowable fill (40%): 0.6104 sq in

Maximum wires: 0.6104 ÷ 0.3039 = 2 wires

Answer: You can fit up to 2 wires of 3/0 AWG THHN in 1-1/4" RMC conduit.