How Many 14 AWG Wires Fit in IMC Conduit?
Complete NEC-compliant fill chart for 14 AWG THHN wires in Intermediate Metal Conduit (IMC) conduit. Maximum wire counts for all standard conduit sizes.
Quick Answer
For 14 AWG THHN wires in IMC conduit at 40% fill (3+ wires):
- • 1/2" IMC: 14 wires
- • 3/4" IMC: 24 wires
- • 1" IMC: 39 wires
14 AWG in IMC Conduit Fill Chart
Conduit Size | Max Wires (40% Fill) | Fill % | Max Wires (Nipple 60%) | Fill % |
---|---|---|---|---|
1/2" | 14 | 40% | 21 | 60% |
3/4" | 24 | 40% | 36 | 60% |
1" | 39 | 39% | 59 | 60% |
1-1/4" | 67 | 39% | 101 | 59% |
1-1/2" | 91 | 40% | 137 | 60% |
2" | 151 | 40% | 227 | 60% |
2-1/2" | 264 | 40% | 396 | 60% |
3" | 399 | 40% | 599 | 60% |
3-1/2" | 517 | 40% | 776 | 60% |
4" | 656 | 40% | 984 | 60% |
Understanding the Fill Chart
According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:
- 1 conductor: 53% fill maximum
- 2 conductors: 31% fill maximum
- 3 or more conductors: 40% fill maximum
- Nipples (24" or less): 60% fill maximum
This chart shows the maximum number of 14 AWG THHN conductors that can fit in each IMC conduit size while maintaining NEC compliance.
Calculation Example
Question: How many 14 AWG THHN wires can fit in 3/4" IMC conduit?
Wire area: 0.0097 sq in per conductor
Conduit internal area: 0.586 sq in
Allowable fill (40%): 0.2344 sq in
Maximum wires: 0.2344 ÷ 0.0097 = 24 wires
Answer: You can fit up to 24 wires of 14 AWG THHN in 3/4" IMC conduit.