How Many 14 AWG Wires Fit in IMC Conduit?

Complete NEC-compliant fill chart for 14 AWG THHN wires in Intermediate Metal Conduit (IMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 14 AWG THHN wires in IMC conduit at 40% fill (3+ wires):

  • • 1/2" IMC: 14 wires
  • • 3/4" IMC: 24 wires
  • • 1" IMC: 39 wires

14 AWG in IMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 14 40% 21 60%
3/4" 24 40% 36 60%
1" 39 39% 59 60%
1-1/4" 67 39% 101 59%
1-1/2" 91 40% 137 60%
2" 151 40% 227 60%
2-1/2" 264 40% 396 60%
3" 399 40% 599 60%
3-1/2" 517 40% 776 60%
4" 656 40% 984 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 14 AWG THHN conductors that can fit in each IMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 14 AWG THHN wires can fit in 3/4" IMC conduit?

Wire area: 0.0097 sq in per conductor

Conduit internal area: 0.586 sq in

Allowable fill (40%): 0.2344 sq in

Maximum wires: 0.2344 ÷ 0.0097 = 24 wires

Answer: You can fit up to 24 wires of 14 AWG THHN in 3/4" IMC conduit.