How Many 2 AWG Wires Fit in EMT Conduit?
Complete NEC-compliant fill chart for 2 AWG THHN wires in Electrical Metallic Tubing (EMT) conduit. Maximum wire counts for all standard conduit sizes.
Quick Answer
For 2 AWG THHN wires in EMT conduit at 40% fill (3+ wires):
- • 1/2" EMT: 1 wires
- • 3/4" EMT: 1 wires
- • 1" EMT: 2 wires
2 AWG in EMT Conduit Fill Chart
Conduit Size | Max Wires (40% Fill) | Fill % | Max Wires (Nipple 60%) | Fill % |
---|---|---|---|---|
1/2" | 1 | 38% | 1 | 38% |
3/4" | 1 | 22% | 2 | 43% |
1" | 2 | 27% | 4 | 54% |
1-1/4" | 5 | 39% | 7 | 54% |
1-1/2" | 7 | 40% | 10 | 57% |
2" | 11 | 38% | 17 | 59% |
2-1/2" | 20 | 40% | 30 | 59% |
3" | 30 | 39% | 45 | 59% |
3-1/2" | 39 | 39% | 59 | 59% |
4" | 50 | 39% | 76 | 60% |
Understanding the Fill Chart
According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:
- 1 conductor: 53% fill maximum
- 2 conductors: 31% fill maximum
- 3 or more conductors: 40% fill maximum
- Nipples (24" or less): 60% fill maximum
This chart shows the maximum number of 2 AWG THHN conductors that can fit in each EMT conduit size while maintaining NEC compliance.
Calculation Example
Question: How many 2 AWG THHN wires can fit in 3/4" EMT conduit?
Wire area: 0.1158 sq in per conductor
Conduit internal area: 0.533 sq in
Allowable fill (40%): 0.2132 sq in
Maximum wires: 0.2132 ÷ 0.1158 = 1 wires
Answer: You can fit up to 1 wires of 2 AWG THHN in 3/4" EMT conduit.