How Many 2 AWG Wires Fit in EMT Conduit?

Complete NEC-compliant fill chart for 2 AWG THHN wires in Electrical Metallic Tubing (EMT) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 2 AWG THHN wires in EMT conduit at 40% fill (3+ wires):

  • • 1/2" EMT: 1 wires
  • • 3/4" EMT: 1 wires
  • • 1" EMT: 2 wires

2 AWG in EMT Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 1 38% 1 38%
3/4" 1 22% 2 43%
1" 2 27% 4 54%
1-1/4" 5 39% 7 54%
1-1/2" 7 40% 10 57%
2" 11 38% 17 59%
2-1/2" 20 40% 30 59%
3" 30 39% 45 59%
3-1/2" 39 39% 59 59%
4" 50 39% 76 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 2 AWG THHN conductors that can fit in each EMT conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 2 AWG THHN wires can fit in 3/4" EMT conduit?

Wire area: 0.1158 sq in per conductor

Conduit internal area: 0.533 sq in

Allowable fill (40%): 0.2132 sq in

Maximum wires: 0.2132 ÷ 0.1158 = 1 wires

Answer: You can fit up to 1 wires of 2 AWG THHN in 3/4" EMT conduit.