How Many 14 AWG Wires Fit in FMC Conduit?
Complete NEC-compliant fill chart for 14 AWG THHN wires in Flexible Metal Conduit (FMC) conduit. Maximum wire counts for all standard conduit sizes.
Quick Answer
Maximum 14 AWG THHN conductors in FMC conduit under NEC Chapter 9, Table 1 (40% for 3 or more, 31% for 2, 53% for 1):
- • 1/2" FMC: 13 wires
- • 3/4" FMC: 22 wires
- • 1" FMC: 33 wires
14 AWG in FMC Conduit Fill Chart
| Conduit Size | Max Wires (Table 1) | Fill % | Max Wires (Nipple 60%) | Fill % | Calculator |
|---|---|---|---|---|---|
| 1/2" | 13 | 39.8% | 19 | 58.1% | Open |
| 3/4" | 22 | 40.0% | 33 | 60.1% | Open |
| 1" | 33 | 39.2% | 50 | 59.4% | Open |
| 1-1/4" | 52 | 39.5% | 79 | 60.0% | Open |
| 1-1/2" | 76 | 39.7% | 115 | 60.0% | Open |
| 2" | 135 | 40.1% | 202 | 59.9% | Open |
| 2-1/2" | 202 | 39.9% | 303 | 59.9% | Open |
| 3" | 291 | 39.9% | 437 | 60.0% | Open |
| 3-1/2" | 396 | 39.9% | 595 | 60.0% | Open |
| 4" | 518 | 40.0% | 777 | 60.0% | Open |
Areas: NEC Chapter 9 Table 4 (FMC) and Table 5 (THHN 14 AWG = 0.0097 sq in), recomputed with this site's calculator data on October 31, 2026. All counts include Chapter 9 Note 7 (round up when the division ends in 0.8 or more), the same rule the calculator applies, so a fill shown slightly above the limit can still be allowed. A count in brackets uses the 31% or 53% limit for two or one conductor. Nipples are 24 inches or shorter.
Understanding the Fill Chart
According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:
- 1 conductor: 53% fill maximum
- 2 conductors: 31% fill maximum
- 3 or more conductors: 40% fill maximum
- Nipples (24" or less): 60% fill maximum
This chart shows the maximum number of 14 AWG THHN conductors that can fit in each FMC conduit size while maintaining NEC compliance.
Calculation Example
Question: How many 14 AWG THHN wires can fit in 1" FMC conduit?
Wire area: 0.0097 sq in per conductor
Conduit internal area: 0.817 sq in
Allowable fill (40%): 0.3268 sq in
Maximum wires: 0.3268 ÷ 0.0097 = 33.69 → 33 wires
Answer: You can fit up to 33 wires of 14 AWG THHN in 1" FMC conduit (39.2% fill). Check it in the calculator.