How Many 14 AWG Wires Fit in FMC Conduit?

Complete NEC-compliant fill chart for 14 AWG THHN wires in Flexible Metal Conduit (FMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 14 AWG THHN wires in FMC conduit at 40% fill (3+ wires):

  • • 1/2" FMC: 12 wires
  • • 3/4" FMC: 20 wires
  • • 1" FMC: 33 wires

14 AWG in FMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 12 39% 18 58%
3/4" 20 38% 31 59%
1" 33 39% 50 59%
1-1/4" 56 40% 84 60%
1-1/2" 78 40% 117 60%
2" 129 40% 194 60%
2-1/2" 216 40% 324 60%
3" 333 40% 500 60%
3-1/2" 435 40% 653 60%
4" 553 40% 830 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 14 AWG THHN conductors that can fit in each FMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 14 AWG THHN wires can fit in 3/4" FMC conduit?

Wire area: 0.0097 sq in per conductor

Conduit internal area: 0.508 sq in

Allowable fill (40%): 0.2032 sq in

Maximum wires: 0.2032 ÷ 0.0097 = 20 wires

Answer: You can fit up to 20 wires of 14 AWG THHN in 3/4" FMC conduit.

Related Tools