How Many 4 AWG Wires Fit in IMC Conduit?
Complete NEC-compliant fill chart for 4 AWG THHN wires in Intermediate Metal Conduit (IMC) conduit. Maximum wire counts for all standard conduit sizes.
Quick Answer
For 4 AWG THHN wires in IMC conduit at 40% fill (3+ wires):
- • 1/2" IMC: 1 wires
- • 3/4" IMC: 2 wires
- • 1" IMC: 4 wires
4 AWG in IMC Conduit Fill Chart
Conduit Size | Max Wires (40% Fill) | Fill % | Max Wires (Nipple 60%) | Fill % |
---|---|---|---|---|
1/2" | 1 | 24% | 2 | 48% |
3/4" | 2 | 28% | 4 | 56% |
1" | 4 | 34% | 6 | 52% |
1-1/4" | 7 | 35% | 11 | 55% |
1-1/2" | 10 | 37% | 16 | 59% |
2" | 17 | 38% | 26 | 58% |
2-1/2" | 31 | 40% | 46 | 59% |
3" | 47 | 40% | 70 | 59% |
3-1/2" | 60 | 39% | 91 | 60% |
4" | 77 | 40% | 115 | 60% |
Understanding the Fill Chart
According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:
- 1 conductor: 53% fill maximum
- 2 conductors: 31% fill maximum
- 3 or more conductors: 40% fill maximum
- Nipples (24" or less): 60% fill maximum
This chart shows the maximum number of 4 AWG THHN conductors that can fit in each IMC conduit size while maintaining NEC compliance.
Calculation Example
Question: How many 4 AWG THHN wires can fit in 3/4" IMC conduit?
Wire area: 0.0824 sq in per conductor
Conduit internal area: 0.586 sq in
Allowable fill (40%): 0.2344 sq in
Maximum wires: 0.2344 ÷ 0.0824 = 2 wires
Answer: You can fit up to 2 wires of 4 AWG THHN in 3/4" IMC conduit.