How Many 8 AWG Wires Fit in RMC Conduit?

Complete NEC-compliant fill chart for 8 AWG THHN wires in Rigid Metal Conduit (RMC) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 8 AWG THHN wires in RMC conduit at 40% fill (3+ wires):

  • • 1/2" RMC: 3 wires
  • • 3/4" RMC: 6 wires
  • • 1" RMC: 9 wires

8 AWG in RMC Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 3 35% 5 58%
3/4" 6 40% 9 60%
1" 9 37% 14 58%
1-1/4" 16 38% 25 60%
1-1/2" 22 39% 33 58%
2" 37 40% 55 59%
2-1/2" 65 40% 98 60%
3" 97 40% 146 60%
3-1/2" 127 40% 191 60%
4" 162 40% 244 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 8 AWG THHN conductors that can fit in each RMC conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 8 AWG THHN wires can fit in 3/4" RMC conduit?

Wire area: 0.0366 sq in per conductor

Conduit internal area: 0.549 sq in

Allowable fill (40%): 0.2196 sq in

Maximum wires: 0.2196 ÷ 0.0366 = 6 wires

Answer: You can fit up to 6 wires of 8 AWG THHN in 3/4" RMC conduit.