How Many 6 AWG Wires Fit in EMT Conduit?

Complete NEC-compliant fill chart for 6 AWG THHN wires in Electrical Metallic Tubing (EMT) conduit. Maximum wire counts for all standard conduit sizes.

Quick Answer

For 6 AWG THHN wires in EMT conduit at 40% fill (3+ wires):

  • • 1/2" EMT: 2 wires
  • • 3/4" EMT: 4 wires
  • • 1" EMT: 6 wires

6 AWG in EMT Conduit Fill Chart

Conduit Size Max Wires (40% Fill) Fill % Max Wires (Nipple 60%) Fill %
1/2" 2 33% 3 50%
3/4" 4 38% 6 57%
1" 6 35% 10 59%
1-1/4" 11 37% 17 58%
1-1/2" 16 40% 24 60%
2" 26 39% 39 59%
2-1/2" 46 40% 69 60%
3" 69 40% 104 60%
3-1/2" 91 40% 136 60%
4" 116 40% 174 60%

Understanding the Fill Chart

According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3 or more conductors: 40% fill maximum
  • Nipples (24" or less): 60% fill maximum

This chart shows the maximum number of 6 AWG THHN conductors that can fit in each EMT conduit size while maintaining NEC compliance.

Calculation Example

Question: How many 6 AWG THHN wires can fit in 3/4" EMT conduit?

Wire area: 0.0507 sq in per conductor

Conduit internal area: 0.533 sq in

Allowable fill (40%): 0.2132 sq in

Maximum wires: 0.2132 ÷ 0.0507 = 4 wires

Answer: You can fit up to 4 wires of 6 AWG THHN in 3/4" EMT conduit.