How Many 6 AWG Wires Fit in EMT Conduit?
Complete NEC-compliant fill chart for 6 AWG THHN wires in Electrical Metallic Tubing (EMT) conduit. Maximum wire counts for all standard conduit sizes.
Quick Answer
For 6 AWG THHN wires in EMT conduit at 40% fill (3+ wires):
- • 1/2" EMT: 2 wires
- • 3/4" EMT: 4 wires
- • 1" EMT: 6 wires
6 AWG in EMT Conduit Fill Chart
Conduit Size | Max Wires (40% Fill) | Fill % | Max Wires (Nipple 60%) | Fill % |
---|---|---|---|---|
1/2" | 2 | 33% | 3 | 50% |
3/4" | 4 | 38% | 6 | 57% |
1" | 6 | 35% | 10 | 59% |
1-1/4" | 11 | 37% | 17 | 58% |
1-1/2" | 16 | 40% | 24 | 60% |
2" | 26 | 39% | 39 | 59% |
2-1/2" | 46 | 40% | 69 | 60% |
3" | 69 | 40% | 104 | 60% |
3-1/2" | 91 | 40% | 136 | 60% |
4" | 116 | 40% | 174 | 60% |
Understanding the Fill Chart
According to NEC (National Electrical Code) Chapter 9, Table 1, the maximum conduit fill percentage depends on the number of conductors:
- 1 conductor: 53% fill maximum
- 2 conductors: 31% fill maximum
- 3 or more conductors: 40% fill maximum
- Nipples (24" or less): 60% fill maximum
This chart shows the maximum number of 6 AWG THHN conductors that can fit in each EMT conduit size while maintaining NEC compliance.
Calculation Example
Question: How many 6 AWG THHN wires can fit in 3/4" EMT conduit?
Wire area: 0.0507 sq in per conductor
Conduit internal area: 0.533 sq in
Allowable fill (40%): 0.2132 sq in
Maximum wires: 0.2132 ÷ 0.0507 = 4 wires
Answer: You can fit up to 4 wires of 6 AWG THHN in 3/4" EMT conduit.